PoC Index

CVE-2022-33174

CRITICAL 9.8EPSS 14.1%

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

CVSS v3.1
7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
CVSS v3.1
9.8 CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CVSS v2.0
5.0 MEDIUMAV:N/AC:L/Au:N/C:P/I:N/A:N
EPSS
14.12% chance of exploitation in the next 30 days, 96th percentile
Nuclei
high · CWE-863
Published
2022-06-13
Updated
2024-08-03

Proof-of-concept exploits (2)

Nuclei templates (1)

References